Data Centre & Electronic Cooling

Castrol ON Immersion Cooling Fluid DC 20
Brand Logo

Castrol ON Immersion Cooling Fluid DC 20

open
DESCRIPTION

Castrol ON Immersion Cooling Fluid DC 20 is a synthetic hydrocarbon based dielectric coolant.

open
APPLICATIONS

Immersion Cooling Fluid DC20 is a single phase coolant designed for use in electrical/electronic cooling systems. It has excellent flow properties and thermal properties. This product also provides a superior oxidative stability, excellent dielectric properties, low temperature properties and excellent hydrolytic stability.

open
ADVANTAGES

Castrol ON Immersion Cooling Fluid DC 15 Advantages:

  • Low viscosity fluid providing excellent flow properties
  • Excellent thermal properties.
  • Superior oxidative stability, low temperature properties and excellent hydrolytic stability.
  • Excellent dielectric properties.
  • Compatible with most commercially available elastomers.
open
TYPICAL CHARACTERISTICS

 

Name Method Units ON Immersion Cooling Fluid DC 20
Viscosity, Kinematic @ 0°C ASTM D445 mm²/s 19.8
Viscosity, Kinematic @ 20°C ASTM D445 mm²/s 9.2
Viscosity, Kinematic @ 40°C ASTM D445 mm²/s 5.1
Viscosity, Kinematic @ 100°C ASTM D445 mm²/s 1.7

Density @ 15,6 °C / 60 °F

ASTM D3321 kg/m3 797

Pour Point

ISO 3016 °C / °F -57/-70

Thermal conductivity @ 40 °C / 104 °F

ASTM D7896 W/mK 0.135

Specific heat capacity @ 40 °C / 104 °F

ASTM E1296 kJ/kgK 2.2

Electrical conductivity @ 25 °C / 77 °F

DIN 51111 pS/m <35

Dielectric strength @ 25 °C / 77 °F

IEC 60156 kV/mm >14
Dielectric breakdown voltage @ 25 °C / 77 °F IEC 60156 kV/mm >35
Dielectric constant @ 25 °C / 77 °F ASTM D924 2.06
Flash Point, COC ASTM D92 °C / °F 169/336
Fire Point, COC ASTM D92 °C / °F 191/376

open
APPROVAL & PERFORMANCE CLAIMS
open
ADDITIONAL INFORMATION

Health & Safety:

Please refer to the relevant health and safety data sheet, a copy of which is freely available to all our customers.

Storage:

All packages should be stored under cover. Where outside storage is unavoidable, drums should be laid horizontally to avoid the possible ingress of water and the obliteration of drum markings. Products should not be stored above 60°C or exposed to hot sun or freezing conditions.

Contact Us

Product Data Sheet

Safety Data Sheet

Castrol ON Immersion Cooling Fluid DC 20
PACK SIZES AVAILABLE
icon
20L
icon
1000L

Request a quote for this product

"*" indicates required fields

This field is hidden when viewing the form
This field is hidden when viewing the form
This field is for validation purposes and should be left unchanged.